EasyManua.ls Logo

Sanyo SPW-C0705DXHN8 - Page 165

Sanyo SPW-C0705DXHN8
242 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-19
W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
1. Outdoor Unit
Unit Specifications (18)
MODEL NAME
W-2WAY ECO-i Capacity Control Outdoor Unit <48 horsepower>
GENERAL MODEL No.
SPW-WC4805DXHN8
COMPONENT OUTDOOR UNIT
SPW-
C1405DXHN8
SPW-
C1405DXHN8
SPW-
C1405DXHN8
POWER SOURCE
380 - 400 - 415 V / 3N / 50 Hz 380 - 400 - 415 V / 3N / 50 Hz 380 - 400 - 415 V / 3N / 50 Hz
PERFORMANCE
Cooling capacity kW (BTU / h) 135.0 (460,700)
Heating capacity kW (BTU / h) 150.0 (511,800)
COP
Cooling standard 3.38
Heating standard 3.79
Heating / Cooling ave.
3.59
UNIT DIMENSIONS
Height mm (in.) 1887 (74
-
9 / 32)
Width mm (in.) 2870 (112-1 / 1)
Depth mm (in.)
890 (Ceiling dimension) (+60)
(35-1 / 32) (+2 - 3 / 8)
Net weight kg (lbs.) 345 (760) 345 (760) 345 (760)
Color (Munsell code) Silky shade (1Y 8.5 / 0.5)
ELECTRICAL RATINGS
Voltage rating V 380 400 415
Cooling
Running amperes A 67.0 64.0 62.0
Power input kW 39.9 39.9 39.9
Power factor % 90 90 90
Heating
Standard
Running amperes A 67.0 64.0 61.0
Power input kW 39.6 39.6 39.6
Power factor % 90 90 90
Low temp.
Power input kW 43.8 43.8 43.8
Starting amperes A 128 128 130
COMPRESSOR
Type - Q'ty Hermetic type x 3 Hermetic type x 3 Hermetic type x 3
Motor output kW 3 + 4.5 x 2 3 + 4.5 x 2 3 + 4.5 x 2
Refrigeration oil
Type FV68S (Ether oil)
Charge amount L 5.9 5.9 5.9
Crankcase heater W 25 + 32 x 2 25 + 32 x 2 25 + 32 x 2
Capacity control %
Refrigerant amount at shipment
kg R410A - 13.0 R410A - 13.0 R410A - 13.0
Refrigerant control
Electronic expansion valve
Defrost method
Reverse-cycle defrost, outdoor unit cycle defrost
Heat exchanger
Tube with plate fins
FAN DEVICE
Type - Q'ty Propeller fan x 1 Propeller fan x 1 Propeller fan x 1
Air circulation m
3
/ min 220 220 220
External static pressure Pa 0 0 0
Motor output (No. of poles) kW 0.7 (8P) 0.7 (8P) 0.7 (8P)
Protective devices High pressure switch, overcurrent (CT method)
TUBING
Refrigerant tubing
Gas tube mm (in.)
ø28.58 (1-1 / 8) (Brazing)
Liquid tube mm (in.)
ø12.7 (1 / 2) (Flare nut)
Balance tube mm (in.)
ø6.35 (1 / 4) (Flare nut)
Drain port
External air temperature operation range °C Cooling: -10 ~ 43 °C (DB) Heating: -20 ~ 15 °C (WB)
Operation sound (Hi) dB-A
67.0 (Quiet mode: 64.0)
Primary accessories
Connection tubing
(ø28.58)
Connection tubing
(ø28.58)
Connection tubing
(ø28.58)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
* Performance, electrical characteristics values and operating sound are based on JIS B8616 package A/C.
(Cooling: Indoor intake air temp. 27°C DB / 19°C WB. Outdoor intake air temp. 35°C DB.)
(Heating [standard]: Indoor intake air temp. 20°C DB. Outdoor intake air temp. 7°C DB / 6°C WB.)
(Heating [low temp.]: Indoor intake air temp. 20°C DB / 15°C WB or less. Outdoor intake air temp. 2°C DB / 1°C WB.)

Table of Contents