Capacity change characteristics
1-7. Capacity Correction Graph According to Tubing Length and Elevation Difference
<Cooling>
Base capacity
change rate
Base capacity
ht
*1
92 90 88 86 84 82 80 78 76
94
96
98
100
%
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150
50
40
30
20
10
0
Equivalent length (m)
Equivalent length (m)
Base capacity
change rate
96
98
100
%
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150
10 20 30 40 50 60 70 80 90 100 110 120 130 140 150
–40
50
40
30
20
10
0
94 93 92 91 90 89 88 87 86 85 84
95
97
99
<Heating>
50Hz
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
1.25
1.15
1.00
1.05
1.05
1.19
1.15
1.07
1.09
1.09
1.03
1.05
1.05
1.11
1.11
1.06
1.07
1.07
1.04
1.05
1.05
* The capacity change
rate due to the
refrigerant tubing length
and elevation difference
for each horsepower
level is found from the
correction coefficient
for that horsepower
from this table
multiplied by the base
capacity change rate
from the graphs at left.
However, even if the
calculated result
exceeds 100%, the
maximum capacity
change rate is 100%.
*1 Sample calculations
Cooling operation
Capacity change rate is 97.52%.
Cooling capacity is 54.6 kW .
Heating operation
Heating capacity is 63.0 kW
Rated performance values
(System: 20 HP, 50 Hz, 50 m equivalent length, 15 m elevation
difference
The cooling capacity and heating capacity for this system are
found as shown below.)
From the table, the correction coefficient for that horsepower
level is found to be 1.15.
From the graph, the base capacity change rate is found to be
92.0%.
92.0% × 1.15 = 97.52%
56.0kW × 97.52% = 54.6kW
From the table, the correction coefficient for that horsepower
level is found to be 1.06.
From the graph, the base capacity change rate is found to be
97.2%.
97.2% × 1.06 = 103.0%
Because the calculation result exceeds 100%, the capacity
change rate is 100%.
63.0kW × 100% = 63.0kW
The positive side for the elevation difference indicates that
the outdoor unit is installed at a higher position than the
indoor units. The negative side indicates the opposite.
Cooling Heating
Item
Type
22.4
28.0
33.5
40.0
45.0
Type
Cooling
capacity
(kW)
Power
consumption
(kW)
Heating
capacity
(kW)
Power
consumption
(kW)
<50Hz models>
70
90
115
130
140
5.93
8.12
9.82
11.6
13.3
25.0
31.5
37.5
45.0
50.0
6.11
7.97
9.84
11.5
13.2
Table of correction coefficients by horsepower (HP)
Equivalent
horsepower
Equivalent length (m)
Elevation difference (m)
Elevation difference (m)
–40
–30
–20
–10
–40
–30
–20
–10
0
2-16
Design of 3-WAY ECO-i SYSTEM