Stranded wire
Ring
pressure
terminal
Strip 10 mm
Wire
Special
washer
Screw
Ring pressure
terminal
Terminal plate
Screw and
Special washer
Ring
pressure
terminal
Wire
(1)
(2)
(3)
(4)
How to connect wiring to the terminal
For stranded wiring
Cut the wire end with cutting pliers, then strip the
insulation to expose the stranded wiring about 10
mm and tightly twist the wire ends.
Using a Phillips head screwdriver, remove the ter-
minal screw(s) on the terminal plate.
Using a ring connector fastener or pliers, securely
clamp each stripped wire end with a ring pressure
terminal.
Place the ring pressure terminal, and replace and
tighten the removed terminal screw using a screw-
driver.
How to set the External static pressure of each type (US Type)
The standard (before shipment) external static pressure is shown in the table below.
When using with a higher static pressure, it is necessary to change to the high static pressure mode.
When using with high static pressure mode, set the indoor unit control board as shown below.
Follow the below procedure while the unit is turned off.
(1) Open the cover of the electrical box and confirm that it is the indoor unit control board.
(2) Connect the short circuit connector to the short circuit pin TP3 (2P: Yellow) of the indoor unit control board.
TP6
TP3
TP1
TP6 TP3
White Yellow Red
External static pressure
75 95 125 165 185
10 15 15 15 15
High static pressure 30 30 40 40 40
Standard
Type
Indoor control board
TP1