4-285
1
2
3
4
5
6
7
8
3-WAY ECO-i SYSTEM Unit Specifi cations
7. Concealed Duct Type (U, US Types)
Indoor unit (A-36)
MODEL No.
SPW-US185XH
Source
220 - 230 - 240 V, single-phase, 50/60 Hz
Controller P.C.B. Ass'y
CR-US075XH (Microprocessor)
Fan (Number...diameter)
mm Centrifugal (1...ø190)
Fan motor
Model...Nominal output W DK8-63G280H...60 W
Source 280 / 340 VDC / 3 phase / 50 Hz
No. of pole...r.p.m. (230V, High) rpm 8P... 1,191
Coil resistance
(Ambient temperature 20°C)
Ω
–
Run capacitor VAC, µF –
Electronic expansion valve
Coil UKV-U032E
Coil resistance (at 20°C)
Ω
ORG – GRY : 46 YEL – GRY : 46
RED – GRY : 46 BLK – GRY : 46
Valve body UKV-25D32
Heat exchanger
Coil Aluminium plate fin / Copper tube
Rows...fi n pitch mm 3...1.4
Face area m
2
0.128
Drain pump
PLD-12230ST-2
Rated V, W AC 230 V, 50 Hz, 12 W
Total head & capacity 850 mm, 400 cc/min
TD831143-00W-3WAY.indb285TD831143-00W-3WAY.indb285 2008/12/0117:24:462008/12/0117:24:46