3-WAY ECO-i SYSTEM Unit Specifi cations
8. Concealed Duct High Static Pressure Type (D Type)
Indoor unit (E)
MODEL No.
SPW-DR964GXH56(A/B)
Source
220 - 230 - 240 V, single-phase, 50 Hz
Controller P.C.B. Ass'y
CR-UXRP71B-B (Microprocessor)
Fan (Number...diameter)
mm Centrifugal (2...ø250)
Fan motor
Model...Nominal output W KFC4X-401B3P...400 W
Source 220 - 230 - 240 V, single-phase, 50 Hz
No. of pole...r.p.m. (230V, High) rpm 4P... 1,211
Coil resistance
(Ambient temperature 20°C)
BRN WHT : 6.159 ORG YEL : 0.87
WHT VLT : 1.08 YEL – BLK : 2.87
VLT – ORG : 0.77 BLK – PNK : 5.98
Safety device
Operating temperature
Open °C 130 ± 5
Close °C (115 ± 5)
Run capacitor VAC, µF 450 VAC, 5.0 µF
Electronic expansion valve
Coil UKV-U023E
Coil resistance (at 20°C)
ORG – GRY : 46 YEL – GRY : 46
RED – GRY : 46 BLK – GRY : 46
Valve body UKV-30D33
Heat exchanger
Coil Aluminium plate fin / Copper tube
Rows...fi n pitch mm 3...2.0
Face area m
2
0.655
TD831143-00W-3WAY.indb308TD831143-00W-3WAY.indb308 2008/12/0117:24:562008/12/0117:24:56