1-261
1
1-2. Major Component Specifi cations
(B) Outdoor Units
SPW-C606VH8
MODEL No.
SPW-C606VH8
Source
380 - 400 - 415 V, 3 phase, 50 Hz
Controller P.C.B. Ass'y
CR-C606VH8 (Microprocessor)
Control circuit fuse 20A
Compressor
Model....number C-9RVN273H0K
Source 246V (DC) / 3phase / 60Hz (Inverter drive)
Nominal output W 3,800
Compressor oil cc 1,400
Coil resistance
(Ambient temperature 25°C)
Ω
C – R : 0.552 R – S : 0.552
C – S : 0.552
Safety control
Overload relay models Excessive current control, Discharge temperature control
Operation temperature
Open °C –
Close °C –
Crank case heater –
Refrigerant amount at shipment
kg R410A - 2.75
High pressure switch
–
Set pressure
OFF kg / cm
2
–
ON kg / cm
2
–
Fan
Number...diameter mm 1...ø490
Air circulation m
3
/ h 3,900
Fan speeds (Max.)
~860 rpm (Inverter drive control)
Fan motor
Model No. SIC-71FW-D8120-4
Source ~280V / 3 phase
No. of pole 8
Nominal output W 120
Heat exchanger
Coil Aluminium plate fin / Copper tube
Rows...fin pitch mm 2...1.4
Face area m
2
0.748
SM830160-03ClassicPAC-iA4.ind261261SM830160-03ClassicPAC-iA4.ind261261 2010/02/1610:26:352010/02/1610:26:35