ECO MULTI SYSTEM Unit Specifications
SM830052
I-70
1
6-2. Major component specifications
Indoor unit (A)
6. Ceiling Mounted Type
MODEL No. SPW-T183GH56
Source 220 - 230 - 240 V / 1 phase / 50 Hz
Controller P.C.B. Ass’y CR-X253GH (Microprocessor)
Fan (Number…diameter) mm Centrifugal (3 … ø 130)
Fan motor
Model…Nominal output W SR4Q-31A5P … 30 W
Source 220 - 230 - 240 V / 1 phase / 50 Hz
No. of pole…r.p.m. (230 V, High) rpm. 4 … 1,111
Coil resistance Ω BRN – WHT : 159.4 ORG – YEL : 75.8
(Ambient temperature 20 °C) WHT – VLT : 26.6 YEL – PNK : 26.6
VLT – ORG : 23.9
Safety device
Operating temperature Open °C 130 ± 5 °C
Close °C Differential 15 deg. (min.)
Run capacitor VAC, µF 440 V, 1.8 µF
Electronic refrigerating control valve
Solenoid control model DKV - MOZS550E0
Coil resistance (at 20 °C) Ω ORG – GRY : 46 , YEL – GRY : 46
RED – GRY : 46 , BLK – GRY : 46
Solenoid control valve model IKV-24D12
Heat exchanger
Coil Aluminum plate fin / Copper tube
Rows…fin pitch mm 2 … 1.7
Face area m
2
0.145
Auto louver motor MC8 D
Auto louver motor…Rated V, Hz, W, rpm. 220 – 240 VAC, 50 Hz, 3 W, 3.3 rpm., 8 P
Coil resistance (at 25 °C) Ω 14,900 Ω ± 8 %
Dew proof heater V, W 240 V, 12 W