Loading...
SM830063
I - 143
1
ECO MULTI SYSTEM Unit Specifications
11-3. Other component specifications
11. 1-Way Air Discharge Semi-concealed-Slim Type (SL Type)
MODEL NO. Indoor Unit SPW-SLR93 ~ 253GH56
Power Transformer ATR-II215TB
Rated
Primary V, Hz AC 230 V, 50 Hz
Secondary 10.2 V, 1.4 A
14 V, 0.5 A
Coil resistance WHT - WHT : 112 BRN - BRN : 0.5
RED - RED : 2.3
Thermal cut off temperature ˚C 150
Thermistor (Coil sensor) PB3M-41E-S4 , PBC-41E-S25 , PBC-41E-S36
Resistance K -10 ˚C : 23.7 ± 5 % , 20 ˚C : 6.5 ± 5 %
-5 ˚C : 18.8 ± 5 % , 30 ˚C : 4.4 ± 5 %
0 ˚C : 15.0 ± 5 % , 40 ˚C : 3.1 ± 5 %
5 ˚C : 12.1 ± 5 % , 45 ˚C : 2.6 ± 5 %
10 ˚C : 9.7 ± 5 %
Thermistor (Room or coil sensor) KTEC-35-S6
Resistance K 0 ˚C : 16.5 ± 5 % , 40 ˚C : 2.7 ± 5 %
5 ˚C : 12.8 ± 5 % , 45 ˚C : 2.2 ± 5 %
10 ˚C : 10.0 ± 5 % , 50 ˚C : 1.8 ± 5 %
20 ˚C : 6.3 ± 5 % , 55 ˚C : 1.5 ± 5 %
30 ˚C : 4.0 ± 5 %
Electronic expansion valve
Valve body IKV-24D12
Coil DKV-MOZS550E0
Drain pump WP20SL-19
Rated AC 230 V, 14.7 W
Float switch FS-0218-103
Rated (Contact rated) DC 12 V, 25 W