Control of W-ECO MULTI SYSTEM
3
TD831077
III - 60
7 How to install the weekly timer
Do not supply power to the
unit or try to operate it until
the tubing and wiring to the
outdoor unit is completed.
No. Accompanying parts Q’ty
Spacer
2
Clampers
2
Operation manual
7 1
Installation manual
8 1
No. Accompanying parts Q’ty
Weekly timer
1 1
Connecting wiring
2
2
Screws M4 × 25
3
2
Wooden screws
4
2
length 1.2 m
651_
8132
728_8132
652_
8132
653_
8132
654_
8132
676_
8132
657_
8132
657_
8132
7 Accessories
¶ Do not twist the control
wiring with the power
wiring or run it in the same
metal conduit, because
this may cause malfunc-
tion.
¶ Install the weekly timer
away from sources of
electrical noise.
¶ Install a noise filter or take
other appropriate action if
electrical noise affects the
power supply circuit of the
unit.
The mounting position for the weekly timer should be
located in an accessible place for control. Never cover
over the weekly timer or recess it into the wall.
(1) Remove the flat-top screw on the bottom of the
back case. When you open up the decorative
cover, you will see two gaps under the weekly
timer. Insert a coin into these gaps and remove the
back case.
When using a wall box for flush mounting
¶ If local codes allow, this weekly timer can be mounted
using a conventional wall box for flush mounting.
(2) Attach the back case with the 2 small screws
provided. Using a screwdriver, push open the cut-
outs on the back case. These holes are for screws.
Use the spacers and take care not to tighten the
screws excessively. If the back case does not sit
well, cut the spacers to a suitable thickness.
(3) Connect the 4 wires to the weekly timer 4P terminal
base. (see next page)
(4) To finish, fit the back tabs of the back case into the
weekly timer and mount it using the flat-top screw.
5
6
Switch box for 1 (no cover)
or switch box for 2 (no cover)
Spacer
M4 × 25
Screws (2)
Weekly
timer
Decorative
cover
Flat-top
screw
Under case
(Back case)
658_
8132
Mounting dimensions for continuous installation
¶ For vertical continuous installation, the space
between the weekly timer and the remote controller
must be 25 mm or more.
CAUTION
Control panel
Decorative
cover
Gap
Gap
Coin
057_0059
2. Optional Controller (weekly timer)
2
Wiring outlet
Wall box
90 mm or more
92 mm or more
from the wall
Spacer
125 mm or more
125 mm or more
84 (Fixing pitch
(back side))
18
1790_M_I