W-ECO MULTI SYSTEM Unit Specifications
TD831077
IV - 11
4
1-2. Major component specifications
1. Outdoor Unit (For R407C)
MODEL No. SPW-CR1503GDYH8
Source 380 - 440 - 415 V / 3 N / 50Hz
Controller P.C.B. Ass’y CR - CR1503GDYH8, CR - DYPTG
Control circuit fuse 250 VAC , 15 A
Compressor
PC (Power Control) AC (Standard) SC (Scroll)
Model … Code No.
C-5RN373H8S ... 80838688 C-5RN373H8C ... 80838588 C-SCN603H8B ... 80966188
Nominal output kW 3.75 3.75 6.0
Compressor oil (ETHER FV68S) cc 2,100 2,100 2,700
Coil resistance V - U: 2.78 V - U: 2.78 V - U: 1.655
(Ambient temperature 25°C) U - W: 2.83 U - W: 2.83 U - W: 1.742
W - V: 2.65 W - V: 2.65 W - V: 1.713
Safety devices
Thermal protector ON / OFF °C 120 ± 5 / 98 ± 11
Microprocessor safety devices Compressor current detection circuit
Compressor discharge gas temperature control
Defective drop detection circuit
Voltage drop detection circuit
Crank case heater VAC, W 240, 32 240, 32 240, 44 × 2
Fusible plug (Operating temp) °C 73 ± 2
High pressure switch ACB - 1TB14W (TUV Approved)
Set pressure ON / OFF kg/cm
2
24 ± 2.0 / 33
Fan (Number … diameter(mm)) Propeller (1 … ø 750)
Fan motor
Model … Nominal output W KFJ8T - 301B3P… 200W
No. of pole … r.p.m. (230 V, High) 8 … 567 r.p.m.
Coil resistance BRN - WHT : 12.01
WHT - VLT : 4.218
VLT - YEL : 9.886
(Ambient temperature 20 °C) WHT - PNK : 12.65
Safety device
Thermal protector ON / OFF °C (115 ± 5) / 130 ± 5
Run capacitor VAC , µF 400 VAC , 15 µF
Heat exchanger
Coil Aluminum plate fin / Copper tube
Rows … fin pitch mm 2 … 2.0
Face area m
2
4.94
Outdoor Unit (A)

Table of Contents