W-ECO MULTI SYSTEM Unit Specifications
IV - 40
TD831077
4
3. 2-Way Air Discharge Semi-concealed Type
Unit specifications (B)
MODEL No. Indoor Unit SPW-SR123GH56 / SPW-S123GH56
POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz
PERFORMANCE Cooling Heating
Capacity kW 3.6 4.2
BTU / h 12,000 14,000
Air circulation (Hi / Me / Lo) m
3
/h 570 / 510 / 430
Moisture removal (High) Liters/h 1.6 —
ELECTRICAL RATINGS
Voltage rating VAC 220 - 230 - 240
Available voltage range VAC 198 – 264
Running amperes A 0.36 - 0.37 - 0.38 0.27 - 0.28 - 0.29
Power input W 75 - 80 - 85 55 - 60 - 65
Power factor % 95 - 94 - 93 93 - 93 - 93
Fan motor locked rotor amperes A 1 - 1 - 1
FEATURES
Controls Microprocessor
Timer ON / OFF Timer (Max. 72 hr)
Fan speeds 3 and Automatic control
Air filter Washable, easy access, long life (2,500 hr)
Refrigerant control Electronic expansion valve
Operation sound (Hi / Me / Lo) dB-A 33 / 30 / 26
Refrigerant tubing connections Flare type
Refrigerant tube diameter Narrow tube mm (in.) 9.52 (3 / 8)
Wide tube mm (in.) 12.7 (1 / 2)
Drain connection 25 A, OD32 mm
Drain pump Max. head 25 cm above drain connection
Remote Controller Optional (RCS-SH80TG)
Refrigerant tubing kit / Accessories Optional / —
Color (Approximate value) Munsell 10Y9.3 / 0.4, RAL 9010-GL
DIMENSIONS & WEIGHT (include ceiling panel) Unit dimensions Package dimensions
Dimensions Height mm (in.) 398 ( 15 - 5 / 8) 519 (20 - 3 / 8)
Width mm (in.) 1,110 (43 - 3 / 4) 1,218 (48 - )
Depth mm (in.) 680 (26 - 3 / 4) 788 (31 - )
Net weight kg (lbs.) 40 ( 88 )
Shipping weight kg (lbs.) 61 ( 135 )
Shipping volume m
3
(cu. ft) 0.498 ( 17.6 )
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 27 °CDB/19 °C WB, Outdoor air temperature 35 °C DB