EasyManua.ls Logo

Sanyo SPW-CR703GDCH8 - Page 231

Sanyo SPW-CR703GDCH8
377 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
W-ECO MULTI SYSTEM Unit Spesifications
TD831077
IV - 96
4
7. Concealed Duct Type
MODEL : SPW-UR363GHN56
SOUND LEVEL :
HIGH 38 dB(A), NC 30 / LOW 31 dB(A), NC 21
CONDITION : Under the unit 1.5 m
SOURCE : 220 - 230 - 240 V, 1 Phase, 50 Hz
REMARKS: 1. Value obtained in the actual place where the unit is installed may be slightly higher than the values
shown in this graph because of the conditions of operation, the structure of the building, the background
noise and other factors.
2. The test results were obtained from an anechoic room.
To evaluate “Noise level” the maximum number of the measured OCTAVE BAND SOUND PRESSURE LEVEL is used.
Read the number on each BAND CENTER FREQUENCIES (horizontal axis) ranging from 63 Hz to 8000 Hz and select
the maximum value (vertical axis) among them.
NOTE
MODEL : SPW-UR483GHN56
SOUND LEVEL :
HIGH 40 dB(A), NC 33 / LOW 33 dB(A), NC 25
CONDITION : Under the unit 1.5 m
SOURCE : 220 - 230 - 240 V, 1 Phase, 50 Hz
1762_U_I
60
50
40
30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
OCTAVE BAND SOUND PRESSURE LEVEL, dB
(0 dB = 0.0002 µbar)
NC-50
NC-40
NC-30
NC-20
1763_U_I
60
50
40
30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
OCTAVE BAND SOUND PRESSURE LEVEL, dB
(0 dB = 0.0002 µbar)
NC-50
NC-40
NC-30
NC-20

Table of Contents