Loading...
Test Run and Others
5
TD831077
V-15
3. Installation Standards
3-4. New refrigerant R407C cannot be used for existing models
1. Compressor specs are different.
When refilling the R22 compressor with R407C, durability
will significantly decrease since some of the materials
used for compressor parts are different.
2. Existing piping cannot be used.
Completely cleaning out residual refrigerating machine oil
is impossible, even by flushing.
3. Refrigerating machine oil differs.
Since R22 refrigerating machine oil is mineral oil, it does
not dissolve in R407C. Therefore, refrigerating machine
oil discharged from the compressor can cause
compressor damage.
R407C
1172_M_I
1173_X_S
R22 refrigerating machine oil Mineral oil (suniso oil)
R407C refrigerating machine oil Synthetic fluid (ether oil)