II - 26
Design of W-ECO MULTI SYSTEM
2
TD831077
4. Installation Instructions
(2) The types 70 and 90 must be bolted down through
vibration insulators tightly to the blocks or platform with
4 anchor bolts.
The unit must sit on the vibra-
tion insulator and platform at
least 10 mm wide at both ends.
(3) The types 190 and 150 must be bolted down through
vibration insulators tightly to the blocks or platform at 6
places including the center of the unit (Section A).
The center portion secure the vibration insulator with
tapping screws by the aid of L-type fittings (local
supply).
The vibration insulator should be secured to the outdoor
unit through two holes equally spaced from the center of
the unit bottom plate. Pitch : 100 mm.
Same dimension for both back and front.
The unit must sit on the vibration insulator and platform
at least 10 mm wide at both ends.
To be level with four anchor bolt securing positions.
2092 925
90
(132)
PC unit AD unit
1683_C_
I
830
CAUTION
Details of anchor bolt installation
1687_C_I
Washer
Vibration
insulator
Platform
Anchor bolt
Unit Bottom plate
10 mm or more
1686_C_I
L-type fitting
(Local supply)
Vibration insulator
Platform
Unit Bottom plate
16
10 mm or more
Tapping screw
Details of Section A
(Main)
Platform
(Vibration insulator)
(Sub)
1684_M_I
A
A
In case of lengthwise platform
(Main)
A
A
(Sub)
Platform (vibration insulator)
1684_M_I
In case of widthwise platform

Table of Contents

Related product manuals