Design of W-ECO MULTI SYSTEM
2
TD831077
4. Installation Instructions
4-5. Shield for horizontal exhaust dis-
charge
It is necessary for you to install an air-discharge chamber
(field supply) to direct exhaust from the fan horizontally if it is
difficult to provide a minimum space of 2 m between the air-
discharge outlet and a nearby obstacle.
In regions with heavy snowfall,
the outdoor unit should be
provided with a solid, raised
platform and snow-proof vents.
4-6. Installing the outdoor unit in heavy
snow areas
In locations where wind-blown snow can be a problem, snow-
proof vents should be fitted to the unit and direct exposure to
the wind should be avoided as much as possible. The
following problems may occur if proper countermeasures are
not taken:
● The fan in the outdoor unit may stop running, causing the
unit to be damaged.
● There may be no air flow.
● The tubing may freeze and burst.
● The condenser pressure may drop because of strong
wind, and the indoor unit may freeze.
4-7. Precautions when installing in heavy
snow areas
a) The platform should be higher than the maximum snow
depth.
b) The 2 anchoring feet of the outdoor unit should be used
for the platform, and the platform should be installed
beneath the air-intake side of the outdoor unit.
c) The platform foundation must be solid and the unit must
be secured with anchor bolts.
d) When installing on a roof subject to strong wind, coun-
termeasures must be taken to prevent the unit from
being overturned.
0029_C_I
1677_C_I
With snow-
proof vents
(High platform)
Without snow-
proof vents
(Low platform)
AVOID
DO
CAUTION