Control of W-ECO MULTI SYSTEM
3
TD831077
III - 2
1. Main Operating Functions
1-1. Room temperature control
*
Operation of L or LL cycle when comp. on.
L
3 min.
3 min. 3 min.
LL
LL
LL
L
1 min.
1 min.
* Operation of LL when comp. off.
* For all units except wall mounted type.
In case of wall mounted type, only LL airflow blows
when thermo. OFF.
(5) When thermo. ON
Cooling operation Auto setting : Conforms to the
procedure of “Fan speed auto
control”
Regular fan speed setting :
Conforms to the set fan speed
Heating operation At start of operation : Con-
forms to the procedure of
“Cold draft prevention”
Later
- Fan speed auto setting :
Conforms to the procedure
of “Fan speed auto control”
- Regular fan speed setting :
Conforms to the set fan
speed
Fan speed auto control : Controlled by T (Room
temp - Set temp)
Supplement
The following heating controls receive priority, while
heating.
(2) Fan operation : Set fan speed
(3) Dry operation : L
(4) When thermo. OFF
Cooling Set fan speed
Heating
* Shift temp (valid while heating, only) is set when
shipped from factory as follows:
+4 deg: all type except wall mounted and floor
standing type
+2 deg: wall mounted type
0 deg: floor standing type
Shift temp can be set with Remote controller from +1
to +10 deg.
The thermostat turns ON / OFF with the following T.
T = Room temp - Set temp
With body thermostat
Room temp = (Body sensor) - (Shift temp*)
+1.0
0
-1.0
Cooling Heating
THERMO. OFFTHERMO. ON
+1.0
0
-1.0
634_8132
T T
Supplement:
(1) After thermo.-on, it will not thermo.-off for 3
minutes due to T .
However, for heating, if the indoor coil E2
temperature ] 64 ˚C, it will thermo.-off within 5
minutes (over load protection).
(2) After thermo.-off, it will not thermo.-on for 1 ~ 3
minute.
For cooling or dehumidifying, it will not thermo.-
on if the indoor coil E1 or E2 temperature < 2 ˚C.
(3) When the system is set for test operation, it will
not thermo.-off for 60 minutes (forced thermo.-
on).
1-2. Fan speed control
(1) Control in special conditions
Reverse cycle
Cooling, dry operation : Set fan speed
start control
Oil recovery control
Heating : OFF
Reverse cycle
OFF or LL
defrost control
Switch over control
When switching over from cooling,dry,
or fan to heating : OFF
When switching over from heating to
cooling, dry, or fan: Set fan speed
3
2
1
H
Me
L
-4
-2
0
H
Me
L
1278_X_I
Cooling
Fan speed changed
every min.
Heating
T(deg) T(deg)