II - 21
2
TD831077
Design of W-ECO MULTI SYSTEM
3. Electrical Wiring
(1) When linking outdoor units in a network (S-net link
system), remove the short plug (CN031, 2P Black,
location: right bottom on the outdoor control PCB)
from all outdoor units except any one of the out-
door units. Otherwise the communication of S-net
link system does not perform.
For a system without link (no connection wiring
between outdoor units), do not remove the short
plug.
(2) Do not install the inter-unit control wiring in a loop.
(3) Don’t install the inter-unit control wiring such as
star branch wiring.
Star branch wiring causes mis-address setting.
(4) If branching the inter-unit control wiring, the num-
ber of branch points should be 10 or less.
(Branches less than 1 m are not included in the total
branch number.)
Outdoor unit Indoor unit Indoor unit Indoor unit
0824_M_I
Indoor unit Indoor unit Indoor unit
Outdoor unit
Indoor unit
NG
NG
Branch point
Outdoor unit Outdoor unit Outdoor unit
0193_M_
I
Indoor unit Indoor unit Indoor unit Indoor unit
Indoor unit
more than 1 m
more than 1 m
Branch
point
10 or less
Indoor unit
Indoor unit Indoor unit Indoor unit
less than 1 m
Indoor unit
CAUTION
Outdoor unit Outdoor unit Outdoor unit
0192_M_I
Prohibited
Prohibited
Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit