ECO MULTI SYSTEM Unit Spesifications
SM830063
I-10
1
1. Outdoor Unit
Unit specifications (H)
MODEL No. Outdoor Unit SPW – CR903GV8
POWER SOURCE 380 - 400 - 415 V / 3 phase / 50Hz
PERFORMANCE Cooling
Capacity kW 28.0
BTU / h 95,500
Air circulation (Hi) m
3
/min(cu. ft/min) 150 (5,300)
ELECTRICAL RATINGS
Voltage rating V 380 - 400 - 415
Available voltage range V 342 – 456
Running amperes A 18.8 - 18.3 - 18.0
Max. running amperes* A 24.2 - 23.6 - 23.1
Power input kW 11.3 - 11.4 - 11.5
Max. power input* kW 14.5 - 14.9 - 15.1
Power factor % 91.3 - 89.9 - 88.9
C.O.P. W/W 2 .48 - 2.46 - 2.43
Compressor locked rotor amperes A 62 - 65 - 67
FEATURES
Controls Microprocessor
Defrost control Reverse cycle, microprocessor control
Service function Sensor temp. recall function
Past service warnings recall function
Refrigerant amount at shipment kg R407C - 11.0
Refrigerant control Electronic expansion valve
Operation sound (Hi) dB-A 58
Compressor Super power control twin rotary compressor
Color (Approximate value) Munsell 5Y8.4 / 0.5, RAL 9002 - GL
REFRIGERANT TUBING
Limit of tubing length m(ft.) 100 (328)
Limit of elevation difference m(ft.) Outdoor unit is higher than indoor unit : 50 (165)
between the two units Outdoor unit is lower than indoor unit : 30 (100)
Refrigerant tube Narrow tube mm (in) 12.7 ( 1 / 2 )
outer diameter Wide tube mm (in) 28.58 (1-1 / 8 )
Refrigerant tubing kit / joint kit Optional
DIMENSIONS & WEIGHT Unit dimensions Package dimensions
Unit dimensions Height mm(in) 1,218 (48 - ) 1,351 (53 - 1 / 4)
Width mm(in) 883 (34 - 3 / 4) 1,047 (41 - 1 / 4)
Depth mm(in) 883 (34 - 3 / 4) 1,005 (39 - 5 / 8)
Net weight kg(lb) 241 ( 532 )
Shipping weight kg(lb) 237 ( 522 )
Shipping volume m
3
(cu. ft.) 1.42 ( 50.1 )
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 27 °C DB / 19.0 °C WB , Outdoor air temperature 35 °C DB
* Full load conditions at Indoor / outdoor capacity ratio 130 %
Cooling: Indoor air temperature 32 °C DB / 22.5 °C WB , Outdoor air temperature 43 °C DB / 25.5 °C WB