EasyManua.ls Logo

Sanyo SPW-U255H - Page 352

Sanyo SPW-U255H
517 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1
1-346
Q
Q
Reference diagram for snow-proof duct - 2
Space requirements for setting - (2)
The models of SPW-C256VH with STK-BDE56E
[Obstacle to the front and rear of unit]
The top and both sides must remain open. Either the obstacle to the front or
the obstacle to the rear must be no taller than the height of the outdoor unit.
Outdoor unit
OP
SPW-C256VH
500 150
Note : Necessary dimensions for the maintenance of the snow-proof duct and installation are noted above.
(1) Single-unit installation
(2) Obstacles on both sides
Installation is possible with the maximum 3 outdoor units.
Dimension Q
If a snow protection duct is attached after the unit is
installed, verify that dimension Q is 500 mm or more.
[Installation in front-rear rows]
The top and both sides must remain open. Either the obstacle to the front or the obstacle
to the rear must be no taller than the height of the outdoor unit.
Min. 300 or more
Min. 1500 or more
Min. P
or more
Min. O
or more
Min. 300
or more
Min. 300
or more
Min. 1000
or more
Min. 300
or more
SM830160-03ClassicPAC-iA4.ind346346SM830160-03ClassicPAC-iA4.ind346346 2010/02/1610:26:542010/02/1610:26:54

Table of Contents

Related product manuals