1-7. Capacity Correction Graph According to Temperature Condition
SPW-C486/606VH8 (For 50 Hz and 60 Hz)
Outdoor unit heating capacity correction cof cient during frosting/defrosting (RH approximately 85%)
Outdoor intake air
temperature
°C WB (85% RH)
-20 -15 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6
Correction coef cient
1.0 1.0 0.97 0.96 0.96 0.95 0.94 0.91 0.89 0.88 0.87 0.87 0.87 0.88 0.89 0.91 0.92 0.95 1.0
To calculate the heating capacity with consideration for frosting/defrosting operation, multiply the heating capacity
found from the capacity graph by the correction coef cient from the table above.
Input coef cient (%) Capacity coef cient (%)
Outdoor air intake temp ( °C DB)
Cooling capacity ratio (maximum capacity) Heating capacity ratio (maximum capacity)
Input coef cient (%) Capacity coef cient (%)
Outdoor air intake temp ( °C DB)
Indoor air intake temp ( °C DB)
Indoor air intake temp ( °C DB)
Indoor air intake temp ( °C WB)
Indoor air intake temp ( °C WB)