1
1-350
Q
Q
Reference diagram for snow-proof duct - 4
Space requirements for setting - (4)
The models of SPW-C366/486VH and SPW-C486 / 606VH8 with STK-BDV80E
[Obstacle to the front and rear of unit]
The top and both sides must remain open. Either the obstacle to the front or
the obstacle to the rear must be no taller than the height of the outdoor unit.
Note : Necessary dimensions for the maintenance of the snow-proof duct and installation are noted above.
(1) Single-unit installation
(2) Obstacles on both sides
Installation is possible with the maximum 3 outdoor units.
[Installation in front-rear rows]
The top and both sides must remain open. Either the obstacle to the front or the obstacle
to the rear must be no taller than the height of the outdoor unit.
Min. 300 or more
Min. 1500 or more
Min. P
or more
Min. O
or more
Min. 300
or more
Min. 300
or more
Min. 1000
or more
Min. 300
or more
Dimension Q
If a snow protection duct is attached after the unit is
installed, verify that dimension Q is 500 mm or more.
Outdoor unit
OP
SPW-C366/486VH
SPW-C486 / 606VH8
500 150
SM830160-03ClassicPAC-iA4.ind350350SM830160-03ClassicPAC-iA4.ind350350 2010/02/1610:26:552010/02/1610:26:55