18
S4179544
Not more than 3 units
should be installed
adjacently.
Wall height
Front side:
Less than 120 cm
Air-intake side:
Less than 40 cm
(Fig. 2-11)
If the wall height is
more than given above,
add measurement h to
the service space.
(Fig. 2-11)
Leave space open
above the unit.
Construct louvers or
other openings in the
wall, if necessary, to
ensure adequate
ventilation.
Provide a solid base (concrete block, beams or
equal), a minimum of 5 cm above ground level to
reduce humidity and protect the unit against pos-
sible water damage and decreased service life.
(Fig. 2-12)
Use anchor bolts or equivalent to bolt down the unit,
reducing vibration and noise.
2-6. Shield for Horizontal Exhaust Discharge
It is necessary for you to install an air-discharge
chamber (field supply) to direct exhaust from the fan
horizontally if it is difficult to provide a minimum space
of 2 m between the air-discharge outlet and a nearby
obstacle. (Fig. 2-13)
Important
In regions with heavy snowfall, the outdoor unit
should be provided with a solid, raised platform
and snow-proof vents.
0027_C_I
40 cm
120 cm h
h
Air intake
side
Front
side
0028_C_I
Min. 5 cm
0029_C_I
CAUTION
Fig. 2-11
Fig. 2-12
Fig. 2-13
Air-intake
side

Table of Contents

Other manuals for Sanyo SPW-X253GH56

Related product manuals