EasyManua.ls Logo

Sanyo SPW-X253GH56 - Concealed-Duct High Static Pressure Type (D Type); It Is Recommended that Space Is Provided; The Minimum Space for Installation and Service Is; This Air Conditioner Is Usually Installed above the

Sanyo SPW-X253GH56
91 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
47
S4179544
77
77
7
D
99
99
9
FM
88
88
8
F
Concealed-Duct High Static Pressure Type
(D Type)
3-30. Required Minimum Space for
Installation and Service
This air conditioner is usually installed above
the ceiling so that the indoor unit and ducts are
not visible. Only the air intake and air outlet
ports are visible from below.
The minimum space for installation and service
is shown in Fig. 3-96.
It is recommended that space is provided (600
× 600 mm) for checking and servicing the
electrical system.
Fig. 3-97 and Table 3-6 show the detailed
dimensions of the indoor unit.
Fig. 3-97
Fig. 3-96
48
25, 36
Table 3-6
A
420
450
B
395
425
C
68
98
Length
Type
Unit : mm
A
310
100100
300
B
50
55
25
500
70
35
940
35
15
81
80
290
(Suspension bolt pitch)
130
23 C 55
0793_D_I
60
90
20
40
55
7 X 100 = 700
4 X 100 = 400
500
980 (Suspension bolt pitch)
4-ø20 Hole for
suspension bolt)
Drain pan
793
940
48
46
16 - ø3.2
Electric box
22 - ø3.2
(Hole for full
circumference)
(Hole for full
circumference)
(274)
100
1010
15
10
10
620
5555
100
100
Refrigerant liquid line (ø 9.52 or ø 6.35)
Refrigerant gas line (ø 19.05 or ø15.88)
Power supply entry
Drain connection (25A, O.D. 32 mm)
Duct connection for suction
Duct connection for discharge
0564_D_I
Air suction side
Refrigerant tubing
Min. 600
Space for
service
Min. 130
Electrical
component
box
Inspection access
(600 X 600)
(25 Type)
Min.
550
Min.
580
(36. 48 Type)
or
Suspension
bolt pitch
Suspension
bolt pitch
980
940
130 290
500
Min. 600
(Space for service)
(mm)
Drain pan
Ceiling face

Table of Contents

Other manuals for Sanyo SPW-X253GH56

Related product manuals