1. Specifications
1
2
3
4
5
I-43
SM830080
1-2 Major Component Specifications
(A) Indoor Units : Concealed Duct Type
MODEL No. SPW-UR253GHN56
Source 220 - 230 - 240 V / 1 phase / 50Hz
Controller P.C.B. Ass’y CR-X253GH (Microprocessor)
Fan (Number…diameter) mm Centrifugal (2 … ø 190)
Fan motor
Model…Nominal output W KFC4X-71B5P … 70 W
Source 220 - 230 - 240 V / 1 phase / 50 Hz
No. of pole…r.p.m. (230 V, High) rpm. 4 … 1,063
Coil resistance BRN WHT : 74.72 ORG YEL : 9.588
(Ambient temperature 20°C) WHT VLT : 19.14 YEL BLK : 10.52
VLT ORG : 10.52 BLK PNK : 21.72
Safety device
Operating temperature Open °C 130 ± 5
Close °C ( 115 ± 5)
Run capacitor VAC, µF 440 VAC, 5 µF
Electronic expansion valve
Coil DKV-MOZS697E0
Coil resistance (at 20°C) ORG GRY : 46 , YEL GRY : 46
RED GRY : 46 , BLK GRY : 46
Valve body IKV-24D12
Heat exchanger
Coil Aluminum plate fin / Copper tube
Rows…fin pitch mm 3 … 1.7
Face area m
2
0.189
Drain pump PJV-1,422
Rated VAC, W AC 230 V, 50 Hz, 12 W
Total head & capacity 500 mm, 400 cc/min