The driver is restarted with a
rotating motor
Start after setting as DC braking, or
rotational speed tracking start
Special potential energy load
Connect suitable braking resistor or braking
unit
Over voltage in Dec
process
Too short Dec time (including
tuning process)
The load inertia is too high
Connect suitable braking resistor or braking
unit
Abnormal of supply voltage
Over voltage in
constant-speed
operating
Abnormal of supply voltage
Special potential energy load
Connect suitable braking resistor or braking
unit
Abnormal of supply voltage or
disconnecting of contactor (relay)
Check supply voltage or seek help from
manufacturer
Improper setting of V/F curve or
torque boost
Adjust V/F curve and torque boost value
Motor blocked or load sudden
change
Incorrect setting of motor
overload protection factor