63
64
Function code
P4.09
Name
Frequency increment
change rate of terminal UP/DOWN
Parameter description
0.01~50.00
Setting range Default value
0.50Hz/s0.01~50.00Hz/s
Function code
P4.10
Name
Output selection of terminal 8
Parameter description
0~10
Setting range Default value
1
Function of open-collector output
P4.11
P4.12
Output selection of relay R1
Output selection of relay R2
0~10
0~10
1
3
Function of relay output
Function of relay output
0
Function
Zero output
Parameter description
Setting range
Output terminal does not have any function
1
2
3
4
5
6
7
8
9
10
Forward rotation running
of inverter
Reverse rotation running
of inverter
Fault output
Reach the frequency level
detection FDT
Reach the frequency
During zero frequency
running
Reach the upper frequency
Reach the lower frequency
Auxiliary pump 1
Auxiliary pump 2
It represents forward rotation running of inverter, there is output
frequency. It outputs signal ON at this moment.
It represents reverse rotation running of inverter, there is output
frequency. It outputs signal ON at this moment.
It outputs signal ON when the inverter comes across fault.
Please refer to the detailed description of function codes P4.13
and P4.14.
Please refer to the detailed description of function code P4.15.
It outputs signal ON when the output frequency of inverter is
lower than the starting frequency.
It outputs signal ON when the running frequency reaches the
upper limit.
It outputs signal ON when the running frequency reaches the
lower limit.
PID one-drive-two
PID one-drive-three
Function code
P4.13
Name
FDT level detection value
Parameter description
0.00~P0.13
Setting range Default value
50.00Hz
0.00~P0.13 (max frequency)
P4.14 FDT lag detection value 0.0~100.0 50.00Hz
0.0~100.0% (FDT level)
Terminal UP/DOWN is used to regulate the change rate for frequency setting.
Setting of detection value of output frequency and lagged value of output
action canceling, as shown in the following drawing:
Chapter 6: Instruction for parameters Chapter 6: Instruction for parameters
Frequency detection signal
(terminal 8, R1, R2)
Output frequency F
FDT level
FDT lag
Time t
Fig.6-10 Schematic diagram of FDT level
Time t
Function code
P4.15
Name
Frequency reaches the
checkout range
Parameter description
0.0~100.00
Setting range Default value
0.0Hz0.0~100.0 %(max frequency)
Function code
P5.02
Name
Selection of motor
overload protection
Description
0~2
Setting range Default value
0
0: Without protection
1: Common motor
(with low-speed compensation)
2: Frequency conversion motor
(without low-speed compensation)
Function code
P5.00
P5.01
Name
Over-voltage stalling
protection
Over-voltage stalling
protection voltage
Parameter description
0~1
Setting range Default value
00: Forbidden 1: Permissible
110~150% (380V series)
110~150 120%
110~150% (220V series)
110~150 115%
When the output frequency of inverter reaches the set value, this function is able
to regulate its checkout range. As shown in following diagram:
During the deceleration running, the actual decrease rate of motor speed
may be lower than decrease rate of output frequency due to the effect of load
inertia, at this moment, motor will feed back the electric energy to the inverter,
and cause the voltage of inverter bus to rise, this would lead to inverter trip due
to over-voltage fault of bus if no measures are taken.
Over-voltage stalling protection function: during running of inverter, it
detects the bus voltage and compares with the over-voltage stalling point
defined by P5.01 (relative to standard bus voltage), if the detected value is
beyond the over-voltage stalling point, output frequency of inverter will stop
falling, when the detected value is lower than the stalling point again, it will
continue to make deceleration running. As shown in diagram 6-12.
0: Without protection. It does not have motor overload protection property
(operation with caution), at this time, inverter does not have overload protection
to the load motor.
Frequency detection signal
(terminal 8, R1, R2)
Output frequency F
Setting frequency
Detection range (P4.15)
Time t
Fig.6-11 Schematic diagram of frequency reaching checkout value
Time t
Group P5 Protection functions