Chapter 1 Safety points and precautions Chapter 1 Safety points and precautions
1.2 Precautions
1.2.1 Examination for motor insulation
The motor should be given the insulation examination when it is used at first time
and reused after long-time no service and when it is checked regularly, to prevent
the inverter being damaged for poor insulation of motor windings. When conducting
the check for insulation, must separate the motor wires from the inverter. It is
suggested that 500V megohmmeter should be used to measure, the measured
insulation resistance should not be less than 5M.
1.2.2 Thermal protection for motor
When the rated capacity of motor doesn't match with that of inverter, especially,
the rated power of inverter is larger than that of motor, please adjust the related
motor-protection parameters inside the inverter or mount a thermal relay in front of
motor additionally to protect the motor.
1.2.3 Running at above power frequency
The inverter can provide the output frequency of 0~600Hz. If user wants it to
run at 50Hz above, please take the bearing capacity of mechanical device into the
consideration.
1.2.4 Vibration of mechanical device
The inverter may meet the mechanical resonant points of load device at some
power frequencies, which can be avoided through setting the hopping frequency
parameters inside the inverter.
1.2.5 Motor heat and noise
Because the inverter output voltage is PWM wave, including the certain harmonic,
the temperature rise, noise and vibration of motor will be increased slightly
compared with that when the inverter runs at power frequency.
1.2.6 Varistor or capacitor for improving the power factor on the output side
Because the inverter outputs PWM wave, if the capacitor for improving the power
factor or lightning-protection varistor is mounted on the output side, the
instantaneous over current is easily produced to damage the inverter, please don't
install them.
1.2.7 Contactors mounted at input and output terminals
If the contactor is mounted between the power supply and inverter input terminal
additionally, it is not allowed to control the start and stop of inverter. If necessary,
the interval of control should not be less than 1hour, because the frequent charge
and discharge will easily reduce the service life of capacitor that is in the inverter. If
the contactor is mounted between the output terminal and motor, please make sure
that the inverter performs the making and breaking operation when it has no output,
otherwise the inverter module will be damaged easily.
1.2.8 Use beyond the rated value
SY8000 series inverter should not be used beyond the permissible working
voltage specified in this manual, otherwise, the inverter parts will be damaged. If
necessary, please use the step-up or stepdown device for transformation treatment.
1.2.9 Changing three-phase input into two-phase input
SY8000 series three-phase inverter is not allowed to be used as two-phase one,
otherwise, the fault or damage of inverter will happen.
1.2.10 Lighting impact protection
The inverter has the lightning over current protection device, so, it has a certain
self-protection ability to resist the induction lightning. For the lighting frequent
occurrence area, a protection device should be mounted in front of inverter.
1.2.11 Altitude and derating use
In the area where the altitude exceeds 1,000m, the heat emission efficiency of
inverter gets bad for the tenuous air, therefore, it is necessary to reduce the
capacity. Please contact us for technology enquiry for this case.
1.2.12 Some special methods
If user needs the connection methods that are not specified in this manual, such
as the common DC bus, please contact us.
1.2.13 Attentions against the rejection of inverter
The electrolytic capacitor at main circuit and the one at the printed board may be
exploded when they are burned. The plastic part may produce the poisonous gas
when it is burned, therefore, they shall be treated as the industrial rubbish.
1.2.14 Applicable motor
1.2.14.1 The standard applicable motor is the four-pole squirrel cage
asynchronous induction motor. If your motor is not the abovementioned one, please
select the inverter according to the rated current of motor. If needing the drive of
permanent magnet synchronous motor, please contact us.
1.2.14.2 The cooling fan of non-frequency conversion motor is connected
coaxially with the rotator, the cooling efficiency of fan is lowered with the rotation
speed, therefore, a strong exhaust fan or frequency-conversion fan is mounted
against too much heat.
1.2.14.3 The inverter has provided the standard parameters of built-in motor,
according to the actual situations, please perform the motor parameter
identification or amend the default to accord with the actual value, otherwise, the
running efficiency and protection performance will be influenced.
1.2.14.4. If the cable or motor inner has the short circuit, the inverter will make
the alarm or it will be exploded, please perform the insulation short-circuit test for
the initially-installed motor and cable, and this test is also often conducted in daily
maintenance. Please pay attention to that when conducting this test, please switch
off the inverter and all tested parts.