Chapter 6: Instruction for parameters Chapter 6: Instruction for parameters
Function code
P9.05
Name
T re a tm e nt f o r
communication
error
Parameter description
0~3
Setting range Default value
3
0: Give an alarm and free stop
1: Continue to run without alarm
2: Stop according to the halt mode without
alarm (only under communication control mode)
3: Stop according to the halt mode without
alarm (under all control modes)
Function code
P9.06
Name
Response operation
of communication
Parameter description
0~1
Setting range Default value
10: Write operation responds
1: Write operation does not respond
When this function code is set at 0.0s, parameter of communication override
time is ineffective.
When this function code is set at effective value, if the interval time between a
communication and the next one goes beyond the communication override time,
the system would report the communication error (ER188).
Under normal conditions, this parameter will be set ineffective. In continuous
communication system, it is able to monitor the communication situation by
setting this parameter.
Under abnormal communication condition, inverter is able to screen the fault
alarm or stop through selecting the protection operation, and keep running.
When this function code is set at 0, the inverter will respond to the read write
command from upper machine.
When this function code is set at 1, the inverter will respond to the read
command from upper machine, but will not respond to the write command, it is
able to improve the communication efficiency through this mode.
Group PA Vector control
Function code
PA.00
PA.01
PA.02
PA.03
PA.04
PA.05
Name
Proportional gain 1 of speed ring
Integral gain 1 of speed ring
Frequency for switching low point
Proportional gain 2 of speed ring
Integral gain 2 of speed ring
Frequency for switching high point
Parameter description
0~100
0.01~10.00
0.00~PA.05
0~100
0.01~10.00
0.00~P0.04
Setting range Default value
20
0.50s
5.00Hz
15
1.00s
10.00Hz
0~100
0.01~10.00s
0.00Hz~PA.05
0~100
0.01~10.00s
0.00Hz~P0.13 (max frequency)
The above parameters are only effective for vector control, but ineffective for
V/F control. When under switching frequency 1 (PA.02), parameter PI of speed
ring is PA.00 and PA.01. When it is above switching frequency 2 (PA.05),
parameter PI of speed ring is PA.03 and PA.04. Between the switching points,
parameter PI is got from line change of two groups of parameters, as shown in
diagram 6-19.
Function code
PA.06
Name
VC slip compensating factor
Parameter description
50~200
Setting range Default value
100%
50%~200%
Function code
PA.07
Name
Upper limit setting of torquer
Parameter description
0.0~200. 0
Setting range Default value
150. 0%
0.0~200.0%
(rated current of inverter)
Function code
PB.00
Name
Self-learning of
motor parameterr
Description
0~2
Setting range Default value
0
0: No operation
1: Overall self-learning of parameter
2: Static self-learning of parameter
It is able to regulate the speed dynamic response of vector control through
setting proportion factor and integral time. It is able to speed up the dynamic
response of speed ring both by adding proportional gain and reducing integral
time, but too large of proportional gain or too short of integral time would lead to
system oscillation and over-large overshoot. However, too small of proportional
gain also may lead to system oscillation and speed steady-state error.
Parameter PI of speed ring has close relationship with inertia of motor system,
users should regulate according to different load requirements on the basis of
default PI parameter, to satisfy demands of various occasions.
Slip compensating factor: it is used for regulating the slip frequency of vector
control, improving speed control accuracy of system, it is able to prevent speed
steady-state error by regulating this parameter suitably.
Setting of 100.0% corresponds to the rated output current of inverter.
Group PB Motor parameter setting
0: No operation, i.e. forbidden to self-learn.
1: Overall self-learning of parameter
Before self-learning of motor parameter, please release the motor from loads
first, let the motor under no-load state, and make sure that the motor is under
static state.
Fig.6-19 Schematic diagram of parameter PI
Parameter PI