Chapter 5 Configuring the PM130 PLUS General Meter Setup
PM130 PLUS Powermeter Series_Installation Operation and Manual 100
Using PAS
Select General Setup from the Meter Setup menu, and then click on the Control/Alarm Setpoints tab.
The following table lists the available setpoint options.
Table 26: Setpoint Options
Display
Label
Option
Range
Description
TriG
Trigger parameter
See Appendix C
The trigger parameter that is used as an argument in the
logical expression
On
Operate limit
The threshold (in primary units) at which the conditional
expression would be evaluated to true. Not applicable for
digital triggers.
OFF
Release limit
The threshold (in primary units) at which the conditional
expression would be evaluated to false. Defines the hysteresis
for analog triggers. Not applicable for digital triggers.
On d
Operate delay
0.1-999.9 sec
The time delay before operation when the operate conditions
are fulfilled
OFFd
Release delay
0.1-999.9 sec
The time delay before release when the release conditions are
fulfilled
Act
Action
See Appendix C
The action performed when the setpoint expression is
evaluated to true (the setpoint is in operated state)
Figure 5-12: General Setup Dialog Box Control/Alarm Setpoints Tab