Chapter 5 Configuring the PM130 PLUS Configuring Recorders
PM130 PLUS Powermeter Series_Installation Operation and Manual 113
To define the contents of the file:
1. Highlight the data log file row with the left mouse button, and then click on the Setup Recorder
button, or click on the Data Recorder tab and select the corresponding log number.
Figure 5-19: Log Setup Dialog Box – Data Recorder Tab
2. Configure the list of parameters to be recorded in a log file. You are not allowed to select more
parameters than you defined when configuring your file. Refer to Appendix D for a list of available
parameters.
3. For your convenience, PAS follows your selection and helps you configure a series of the
neighboring parameters: when you open the Group box for the next parameter, PAS highlights
the same group as in your previous selection; if you select this group again, PAS automatically
updates the Parameter box with the following parameter in the group.
4. Add the name for your data log file in the Name box. It will appear in the data log reports.
5. Save your new setup to the device database, and send it to the meter.
Billing/TOU Daily Profile Log File
Data log #16 is configurable to store TOU daily profile log records on a daily basis.
The file is organized as a multi-section file that has a separate section of the same structure for each billing
energy and maximum demand register. The number of sections is taken automatically from the Billing/TOU
Registers setup (see Configuring Billing/Tariff Registers). If the maximum demand profiling is used, then
the number of sections in the file will be twice the number of the allocated billing registers.
To configure a daily profile log file:
1. Configure your Billing/TOU registers and tariff schedule in the meter (see Configuring Billing/Tariff
Registers) first.
2. Double click on the Data Log#16 partition with the left mouse button.