Chapter 5 Configuring the PM130 PLUS Configuring Communication Protocols
PM130 PLUS Powermeter Series_Installation Operation and Manual 116
5.6.2 Configuring DNP3
Refer to the PM130 DNP3 Reference guide for information on the DNP3 protocol implementation and a
list of the available data points.
DNP Options
Select Protocol Setup from the Meter Setup menu and click on the DNP Options tab.
Figure 5-21: Protocol Setup Dialog Box DNP Options Tab
The following table describes available options. Refer to the DNP3 Data Object Library document available
from the DNP User’s Group on the DNP3 object types.
Table 30: DNP Options
Parameter
Options
Default
Description
Binary Inputs (BI)
Binary Input Object
Single-bit
With Status
Single-bit
The default BI object variation for requests with qualifier
code 06 when no specific variation is requested
Analog Inputs (AI)
Analog Input Object
32-bit
32-bitFlag
16-bit
16-bitFlag
16-bit-Flag
The default AI object variation for requests with qualifier
code 06 when no specific variation is requested
Binary Counters (BC)
Binary Counter
Object
32-bit+Flag
32-bitFlag
16-bit+Flag
16-bitFlag
32-bit-Flag
The default BC object variation for requests with qualifier
code 06 when no specific variation is requested