Appendix F Data Scales
PM130 PLUS Powermeter Series_Installation Operation and Manual 171
Appendix F Data Scales
The maximum values for volts, amps and power in the PM130 PLUS setup and in communications are
limited by the voltage and current scale settings. See Device Options in Chapter 4 on how to change the
voltage and current scales in your meter.
The following table shows the meter data scales.
Table 39: Data Scales Values
Scale
Conditions
Range
Maximum voltage
(V max)
All configurations
Voltage scale PT Ratio, V
1
Maximum current
(I max)
All configurations
Current scale CT Ratio, A
2, 3
Maximum Power
4
Wiring 4LN3, 3LN3, 3BLN3
V max I max 3, W
Wiring 4LL3, 3LL3, 3BLL3, 3OP2, 3OP3, 3DIR2
V max I max 2, W
Maximum frequency
25, 50 or 60 Hz
100 Hz
400Hz
500 Hz
1
The default voltage scale is 144V. The recommended voltage scale is 120V+20% = 144V for using with
external PT’s, and 690V+20% = 828V for a direct connection to power line.
2
CT Ratio = CT primary current/CT secondary current
3
The default current scale is 2 CT secondary (2.0A with 1A secondary and 10.0A with 5A secondary).
4
Maximum power is rounded to whole kilowatts. With PT=1.0, it is limited to 9,999,000 W.