EasyManua.ls Logo

Satec PM130 PLUS Series - Wiring Diagrams

Satec PM130 PLUS Series
176 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 2 Installation Electrical Installation
PM130 PLUS Powermeter Series_Installation Operation and Manual 28
2.4.6 Wiring Diagrams
For AC input ratings, see Technical Specifications in Appendix A for more details.
Table 2 presents the available wiring configurations in the meter. For more details, see Basic Meter Setup
in Chapter 5.
Table 2: Wiring Configurations
Wiring Configuration
Setup Code
Figure
3-wire 2-element Delta direct connection using 2 CTs
3dir2
2-9
4-wire 3-element Wye direct connection using 3 CTs
4Ln3 or 4LL3
2-10
4-wire 3-element Wye connection using 3 PTs, 3 CTs
4Ln3 or 4LL3
2-11
3-wire 2-element Open Delta connection using 2 PTs, 2 CTs
3OP2
2-12
4-wire 2½-element Wye connection using 2 PTs, 3 CTs
3Ln3 or 3LL3
2-13
3-wire 2½-element Open Delta connection using 2 PTs, 3 CTs
3OP3
2-14
4-wire 3-element Delta direct connection using 3 CTs
4Ln3 or 4LL3
2-15
3-wire 2½-element Broken Delta connection using 2 PTs, 3 CTs
3bLn3 or 3bLL3
2-16
3-wire/4-wire connection using the current from one phase (1 CT) and the L-L
voltage from the other two phases
2LL1
2-17/18
3-wire/4-wire connection using the current from one phase (1 CT) and the L-L
voltage from the other two phases
1LL3
2-19/20
Figure 2-9 3-Wire 2-Element Delta Direct Connection Using 2 CTs (Wiring Mode = 3dir2)

Table of Contents