Chapter 2 Installation Electrical Installation
PM130 PLUS Powermeter Series_Installation Operation and Manual 28
2.4.6 Wiring Diagrams
For AC input ratings, see Technical Specifications in Appendix A for more details.
Table 2 presents the available wiring configurations in the meter. For more details, see Basic Meter Setup
in Chapter 5.
Table 2: Wiring Configurations
3-wire 2-element Delta direct connection using 2 CTs
4-wire 3-element Wye direct connection using 3 CTs
4-wire 3-element Wye connection using 3 PTs, 3 CTs
3-wire 2-element Open Delta connection using 2 PTs, 2 CTs
4-wire 2½-element Wye connection using 2 PTs, 3 CTs
3-wire 2½-element Open Delta connection using 2 PTs, 3 CTs
4-wire 3-element Delta direct connection using 3 CTs
3-wire 2½-element Broken Delta connection using 2 PTs, 3 CTs
3-wire/4-wire connection using the current from one phase (1 CT) and the L-L
voltage from the other two phases
3-wire/4-wire connection using the current from one phase (1 CT) and the L-L
voltage from the other two phases
Figure 2-9 3-Wire 2-Element Delta Direct Connection Using 2 CTs (Wiring Mode = 3dir2)