2.5.2 DC Current measurement (Hall Effect Sensors)
The device has 3 independent currents rated at 20mA nominal current to which the user may connect
standard Hall Effect sensors featuring 0-20mA/+-20mA outputs.
DC power is calculated with indication for direction of power flow.
Energy for each channel is calculated separately.
Typical Current measurement accuracy: better that 0.5% (depending on HES type)
It is recommended to use Satec HEPS +-15VDC independent power supplies as the HACS
Notes:
It is mandatory to use cabling featuring double insulation (600V) when connecting HE sensors to
the meter
It is mandatory to use a separate power supply for each sensor.
Requirements for power supply for Hall Effect Sensors:
Double insulation
No Ground connection permitted
Overvoltage withstand of 3kV or more
Satec HEPS (Hall effect sensor power supply) or: 15V DC or +/- 15VDC (or 12VDC) power supply,
depending on HSE type
UL Listed
DC power is calculated with indication for power flow direction.
Energy is calculated for each channel separately.
Typical Current measurement accuracy: better that 0.5% (depending on HES type)