Chapter 2 Installation Communications Connections
PM130 PLUS Powermeter Series_Installation Operation and Manual 47
2.7.3 PRO module – COM2 PROFIBUS Connection
Figure 2-34 COM2 PROFIBUS Connection
• The PRO module TERMINAL is for use only with equipment which has no live parts which are
ACCESSIBLE
• The RATING of the insulation of the external equipment for use with the PRO module, shall
comply according to Installation Category II for insulation to be suitable for SINGLE FAULT
CONDITION
• The external equipment TERMINAL connection type is DB9
• The type of equipment that might be connected to the TERMINAL is:
o Programmable Logic Controller for automation – PLC