Chapter 3 Using Front Display Data Display
PM130 PLUS Powermeter Series_Installation Operation and Manual 55
3.2.3 Simple Reset of Accumulated Data
You can clear the Min/Max log, maximum demands or energies from the data display mode without
accessing the reset menu with the simple “two-button” reset option:
1. Select a display page where the data you want to reset is displayed:
Min/Max log: select a Min/Max page from the Min/Max Display
Ampere and volt maximum demands: select the Ampere or Volt maximum demand page from the
Min/Max Display.
Power maximum demands: select the power maximum demand page from the Min/Max Display.
Total and phase energies: select a total energy, or a phase energy page from the Energy Display.
2. While holding the SELECT button down, press and hold the ENTER button for about 5 seconds.
The displayed data is reset to zero.
This function is not operational if the meter is password protected and the simple reset is not allowed in
protected mode (see Configuring the Display).
3.2.4 Common Measurements Display
Scroll through pages with the UP and DOWN arrow buttons.
Table 3: Common Measurements (Regular version)
1
L
V12
V23
V31
Line-to-line volts
2
P
V1
V2
V3
Line-to-neutral volts (in 4LN3, 3LN3, 3BLN3 configurations)
3
I1
I2
I3
Amps
4
kVA/MVA
PF
kW/MW
Total VA
Total PF
Total W
5
In
Hz
kvar/Mvar
Neutral current
Frequency
Total var
6
Ph.L1
PF
kW/MW
Phase L1 powers
(if enabled)
7
kVA/MVA
Ph.L1
kvar/Mvar
Phase L1 powers
(if enabled)
8
Ph.L2
PF
kW/MW
Phase L2 powers
(if enabled)
9
kVA/MVA
Ph.L2
kvar/Mvar
Phase L2 powers
(if enabled)