Chapter 3 Using Front Display Using the Menus
PM130 PLUS Powermeter Series_Installation Operation and Manual 64
3.3.3 Diagnostics Display
The diagnostics display shows a list of the device diagnostic codes recorded as a result of the meter self-
test diagnostics during start-up and operation. When there are recorded diagnostic messages, the “i”
diagnostic LED on the front display briefly flashes two times to indicate that the meter may require
servicing.
The diagnostic LED can be disabled or enabled via the display setup menu (see Configuring the Display).
Use the UP and DOWN arrow buttons to scroll through the diagnostic message list. See Device Diagnostic
Codes in Appendix G for the list of diagnostic codes and their meanings.
Frequent hardware failures may be the result of excessive electrical noise in the region of the device. If
the meter continuously resets itself, contact your local distributor.
A configuration reset may also be a result of the legal changes in the meter configuration when other
configuration data is affected by the changes.
The diagnostics codes are stored in a non-volatile register, which is not affected by loss of power and may
be cleared via communications (see Viewing and Clearing Device Diagnostics in Chapter 6) or from the
meter display.
To clear the meter diagnostics:
1. Select a diagnostics page.
2. While holding the SELECT button, press and hold the ENTER button for about 5 seconds until
the diagnostic message is reset to none.
3.4 Using the Menus
3.4.1 Navigation Buttons
The PM130 PLUS has a menu-driven setup. Press and release the SELECT button to access the meter
menus.
See the following table for button operations in menus.
Button
Action
Operations
SELECT
Press and release
Highlight (activate) a menu window.
UP
Press and release
Scroll through menu items forwards or increment a number in the
highlighted window. Hold down the button for continuous scrolling.
DOWN
Press and release
Scroll through menu items backwards or decrement a number in the
highlighted window. Hold down the button for continuous scrolling.
ENERGY/ENTER
Press and release
Confirm the selection and store the changed item or perform an action
indicated in a highlighted window.
H/ESC
Press and release
Quit the highlighted window without saving a selected item or return to
the upper-level menu.

Table of Contents