Chapter 5 Configuring the PM130 PLUS Configuring Communications
PM130 PLUS Powermeter Series_Installation Operation and Manual 76
Table 15: COM Port Options
Display
Label
Parameter
Options
Default
Description
Prot
Protocol
ASCII = SATEC ASCII
rtu = Modbus RTU
dnP3 = DNP3
PrFb = Profibus DP (COM2)
Modbus RTU
The communications protocol for
the port
Not changeable on COM2 with
the Profibus module
rS
Interface
COM1: 485 = RS-485
COM2:
232 = RS-232
485 = RS-485
422 = RS-422
Eth = Ethernet
PrFb = Profibus DP
GPrS = GPRS modem
RS-485
Communication interface.
Not changeable on COM2 with
the Ethernet and Profibus
modules
Addr
Device address
SATEC ASCII: 0-99
Modbus: 1-247
DNP3: 0-65532
Profibus: 0-126
1
(126 for Profibus)
Device network address
bAud
Baud rate
300 bps-115.2 kbps
9600 bps
The port baud rate
dAtA
Data format
7E, 8N, 8E
8N
Data format and parity. 7E data
format should not be used with
the Modbus RTU and DNP3
protocols
dLAY
Response delay
0-1000 ms
5 ms
The minimum time after the last
request character is received to
start the transmission.
CPtb
ASCII
compatibility
mode
diS = Disabled
En = Enabled
Disabled
Enables a low-resolution device
emulation for ASCII request “0”
in high-resolution devices (see
Device Options)
NOTES:
1. The meter provides the permanent Modbus TCP server on port 502.
2. Selecting the DNP3 protocol launches the second DNP3 TCP server in addition to the Modbus
server allowing simultaneous connections on both ports. Selecting the Modbus protocol disables
the DNP3 TCP server.
3. When you change the COM2 settings through the Ethernet port, the device port restarts so
communications will be temporarily lost. You may need to wait some additional time until PAS
restores a connection with your device.