Chapter 5 Configuring the PM130 PLUS Configuring Communications
PM130 PLUS Powermeter Series_Installation Operation and Manual 78
Table 16: Ethernet Setup Options
502 = Modbus/TCP
20000 = DNP3/TCP
NOTES
1. The meter provides the permanent Modbus TCP server on port 502.
2. Selecting the DNP3 TCP service port launches the second DNP3 TCP server allowing
simultaneous connections on both TCP ports. Selecting the Modbus TCP port disables the DNP3
TCP server.
The TCP service port can also be changed trough the COM2 serial port setup. Changing the
communication protocol for the port automatically changes the TCP port for the Ethernet.
3. When you change the device network settings through the Ethernet port, the device port restarts
so communication will be temporarily lost. You may need to wait some additional time until PAS
restores a connection with your device.
5.1.3 Setting Up GPRS Network
The PM130 PLUS can provide wireless GPRS communications with the remote Modbus/TCP server via
GPRS modem module. See Connecting a GSM/GPRS modem in Chapter 2 on how to connect a modem
to your meter.
To set up GPRS communications:
1. Select Communications Setup from the Meter Setup menu, and then click on the GPRS Setup
tab.
Figure 5-3: Communication Setup Dialog Box – GPRS Setup Tab