Chapter 5 Configuring the PM130 PLUS Configuring Communications
PM130 PLUS Powermeter Series_Installation Operation and Manual 84
5.1.5 Setting Up eXpertPower Client
The PM130 PLUS has an embedded eXpertPowerTM client that provides communications with the
eXpertPowerTM server the SATEC proprietary Internet services. Connections to the eXpertPowerTM
server are handled on a periodic basis.
To set up communications with the eXpertPowerTM server, select Communication Setup from the Meter
Setup menu, and then click on the ExpertPower Client Setup tab.
Figure 5-4: eXpertPower Client Setup Tab
The following table lists available options. Refer to your eXpertPower service provider for the correct
network settings.
Table 18: eXpertPower Client Setup Options
Parameter
Options
Default
Description
XPW Server IP Address
207.232.60.18
The IP address of the eXpertPower server
XPW Server Port
0-65535
5001
The TCP service port of the eXpertPower server
XPW Client Enabled
NO, YES
NO
Enables operations of the eXpertPower client
Time to Next Session, min
1-99999
The time remaining to the next connection session
NOTES
1. Do not enable the eXpertPower client in your meter if you do not use the eXpertPowerTM service.
2. Do not change the connection time setting. It is for information only. The eXpertPower server
updates it automatically.