EasyManua.ls Logo

Satec PM130 PLUS Series - Setting up TCP Notification Client

Satec PM130 PLUS Series
176 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 5 Configuring the PM130 PLUS Configuring Communications
PM130 PLUS Powermeter Series_Installation Operation and Manual 85
5.1.6 Setting Up TCP Notification Client
The TCP notification client can establish connections with a remote Modbus/TCP server and send
notification messages either on events, or periodically on a time basis.
To set up communications with a remote TCP Notification server, select Communication Setup from the
Meter Setup menu, and then click on the TCP Notification Client Setup tab.
Figure 5-5: TCP Notification Client Setup Tab
The following table lists available client options.
Table 19: TCP Notification Client Setup Options
Parameter
Options
Default
Description
Client Enabled
NO, YES
NO
Enables operations of the notification client
Server IP Address
192.168.0.3
The IP address of the notification server
Server Port
0-65535
502
The TCP service port of the notification server
Message Exchange
Address
0-65535
1000
The start address of a block of 16 Modbus registers for receiving
notification messages
Connections with a remote server are triggered via programmable setpoints. To send event notifications
to a server, configure a setpoint to respond to desired triggers or to periodic time events and put the
"Notification" action to the setpoint action list (see Configuring Alarm/Control Setpoints).
See the PM130 PLUS Modbus Reference guide for more information on operation of the notification client
and the notification message structure.