Chapter 5 Configuring the PM130 PLUS General Meter Setup
PM130 PLUS Powermeter Series_Installation Operation and Manual 86
5.2 General Meter Setup
5.2.1 Basic Meter Setup
This section describes how to configure the PM130 PLUS for your particular environment and application.
Before operating your meter, provide the device with basic information about your electrical network.
Using the Front Display
Select the baSc entry from the main menu. See Viewing and Changing Setup Options in Chapter 3 for
information on configuring parameters via the front display.
See the table below for the Basic Setup options.
Using a shortcut to the Basic Setup menu:
From the Data Display, press and release the SELECT button to enter the primary meter menu and then
simultaneously press the SELECT and UP buttons. You are directly moved to the CT setting entry.
The shortcut is not operational if the meter is password protected.
Using PAS
Select General Setup from the Meter Setup menu. See the table below for the Basic Setup options.
Table 20: Basic Setup Options
The wiring connection of the device
The phase potential transformer’s primary to
secondary ratio
PT Ratio multiplication factor. Used in extra high
voltage networks to accommodate the PT ratio for
500 kV and higher networks.
The primary rating of the phase current transformer
The nominal line frequency
Maximum Demand
Load Current
The maximum demand load current (0 = CT
primary current)
Power block
demand period
E,
EH
1, 2, 3, 5, 10, 15,
20, 30, 60 min,
E=external sync
The length of the demand period for power
demand calculations. If the external
synchronization is selected, a pulse front on the
digital input DI1 denotes the start of the demand
interval.