Chapter 5 Configuring the PM130 PLUS General Meter Setup
PM130 PLUS Powermeter Series_Installation Operation and Manual 89
Using PAS
Select General Setup from the Meter Setup menu, and then click on the Device Options tab.
Table 22 lists available device options.
Table 22: User-configurable Device Options
Display
Label
Parameter
Options
Default
Description
P.cAL
Power Calculation
Mode
rEAc = using reactive
power S=f(P, Q),
nAct = using non-active
power Q=f(S, P)
S=f(P, Q)
The method used for calculating reactive and
apparent powers (see Power Calculation Modes
below)
roLL
Energy Roll Value
E, EH
10.E4 = 10000 kWh
10.E5 = 100000 kWh
10.E6 = 1000000 kWh
10.E7 = 10000000 kWh
10.E8 = 100000000 kWh
10.E9 = 1000000000 kWh
10000000
The value at which energy counters roll over to
zero
Ph.En
Phase Energy
Calculation
E, EH
diS = Disabled
En = Enabled
Disabled
Enables phase energy calculations
tESt
Energy Test
Mode
E, EH
OFF = disabled
Ac.Ei = Wh pulses
rE.Ei = varh pulses
Disabled
Setting this option puts the meter into the energy
test mode (see Energy Pulse LED in Chapter 3)
U.Str
Starting Voltage
1.5-5.0%
1.5%
The device starting voltage in percent of FS
(120V or 400V)
rESL
Device Resolution
Lo = Low
Hi = High
Low
The voltage, current and power resolution on the
front display (see Measurement Units in Chapter
3) and in communications (see communication
guides)
U.ScL
Volts Scale, V
60-828 V
144 V
The maximum voltage scale allowed, in
secondary volts. See Data Scales in Appendix F
C.ScL
Amps Scale, A
1.0-10.0 A
2 CT
secondary
The maximum current scale allowed, in
secondary amps. See Data Scales in Appendix F
C.Mod
DC/AC mode
aC = AC
dC = DC
aC
Current’s mode (AC or DC). This option appears
on HACS CT type
Device ONLY.