5.2.4 Configuring Relay Outputs
The PM130 PLUS can be provided with two optional relay outputs. Each relay can be operated either
locally from the alarm/control setpoints in response to an event or by a remote command sent through
communications. It can also be linked to an internal pulse source to produce energy pulses.
Using the Front Display
Select reL from the main menu. This menu entry appears only if the digital I/O module is plugged into the
meter.
Use the UP and DOWN arrow buttons to scroll to the required relay.
To select a relay parameter:
1. Press the SELECT button to activate the middle window.
2. Use the UP and DOWN arrow buttons to scroll to the required parameter.
To change the parameter value:
3. Press the SELECT button to activate the lower window.
4. Use the UP and DOWN arrow buttons to select the required value.
5. Press ENTER to confirm the new parameter setting or press ESC to discard changes.
6. You are returned to the middle window and can configure other relay parameters.
To store your new settings:
1. Press the ENTER button when the middle window is highlighted.
2. You are returned to the upper window and can select another relay output or exit the menu.
3. Press ESC to exit the menu.
See Table 24 for the available relay outputs options.
Using PAS
Select General Setup from the Meter Setup menu, and then click on the Relay Outputs tab.
Figure 5-9: General Setup Dialog Box Relay Outputs Tab
The available relay outputs options are shown in Table 24.
Table 24: Relay Output Options