Chapter 5 Configuring the PM130 PLUS General Meter Setup
PM130 PLUS Powermeter Series_Installation Operation and Manual 95
5.2.5 Configuring Analog Outputs
The meter can be ordered with two optional analog outputs with options for 0-1mA, ±1mA, 0-20mA and
4-20mA current outputs.
Using the Front Display
Select Aout from the main menu. This menu entry appears only if the optional analog output module is
plugged into the meter.
Use the UP and DOWN arrow buttons to scroll to the required analog output.
To select the analog output option:
1. Press the SELECT button to activate the middle window.
2. Use the UP and DOWN arrow buttons to scroll to the required parameter.
To change the parameter value:
1. Press the SELECT button to activate the lower window.
2. Use the UP and DOWN arrow buttons to select the required value.
3. Press ENTER to confirm the new parameter setting or press ESC to discard changes.
4. You are returned to the middle window and can configure other parameters.
To store your new settings:
1. Press the ENTER button when the middle window is highlighted.
2. You are returned to the upper window and can select another analog output or exit the menu.
3. Press ESC to exit the menu.
See Table 25 for the available analog output options.
Using PAS
Select General Setup from the Meter Setup menu, and then click on the Analog Outputs tab.