EasyManua.ls Logo

Schaltbau CP1115/12 - Page 35

Default Icon
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
35
2021-04-12 / V1.1
Contactors CP Series – Installation and Maintenance Instructions
Maintenance
Installing the xed contacts
NO/NC contactors with arc chambers:
X
Place the new xed contact (2) on the contact car-
rier surface.
X
Push the xed contact (2) towards the centre of
the magnetic drive as far as it will go.
X
Make sure that the xed contact on the contact
support side is tightly in touch with the contact
carrier surface.
X
Tighten the xed contact with the two screws:
- First tighten the inner screw (1a).
- Then screw in the outer screw (1b).
X
For 600 A devices, place the bracket (3) on the
xed contact as shown in Fig. 38 and screw on the
bracket together with the xed contact using the
screw (1a) and the washer.
X
Tighten both screws to the specied torque:
- For 1,200 A and 2,000 A devices with 12 Nm.
- For 600 A devices with 7 Nm.
- First tighten the inner screw (1a), then the outer
screw (1b).
X
To install the second xed contact (2) repeat the
steps above.
1a
2
1b
1a
1b
1,200 A
2,000 A
12
Nm
1,200 A
2,000 A
12
Nm
2
Fig. 37: 1,200 A and 2,000 A NO/NC contactors with arc cham-
bers – install the xed contacts
1a
2
1b
1a
1b
7
Nm
(
600 A
)
7
Nm
(
600 A
)
2
3
3
Fig. 38: 600 A NO/NC contactors with arc chambers – install
the xed contacts

Table of Contents