Contactors CP Series – Installation and Maintenance Instructions
Maintenance
Installing the xed contacts
NO/NC contactors with arc chambers:
X
Place the new xed contact (2) on the contact car-
rier surface.
X
Push the xed contact (2) towards the centre of
the magnetic drive as far as it will go.
X
Make sure that the xed contact on the contact
support side is tightly in touch with the contact
carrier surface.
X
Tighten the xed contact with the two screws:
- First tighten the inner screw (1a).
- Then screw in the outer screw (1b).
X
For 600 A devices, place the bracket (3) on the
xed contact as shown in Fig. 38 and screw on the
bracket together with the xed contact using the
screw (1a) and the washer.
X
Tighten both screws to the specied torque:
- For 1,200 A and 2,000 A devices with 12 Nm.
- For 600 A devices with 7 Nm.
- First tighten the inner screw (1a), then the outer
screw (1b).
X
To install the second xed contact (2) repeat the
steps above.
1a
2
1b
1a
1b
1,200 A
2,000 A
12
Nm
1,200 A
2,000 A
12
Nm
2
Fig. 37: 1,200 A and 2,000 A NO/NC contactors with arc cham-
bers – install the xed contacts
1a
2
1b
1a
1b
7
Nm
(
600 A
)
7
Nm
(
600 A
)
2
3
3
Fig. 38: 600 A NO/NC contactors with arc chambers – install
the xed contacts