EasyManua.ls Logo

Seg HighTECH Line - Page 26

Seg HighTECH Line
42 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
26 TD_MRI1_06.05_GB
6.4.2 Example of test circuit for MRI1
relays without directional feature
For testing MRI1 relays without directional feature,
only current input signals are required. Figure 6.1
shows a simple example of a single phase test circuit
with adjustable current energizing the MRI1 relay un-
der test.
Figure 6.1: Test curcuit
6.4.3 Checking the input circuits and
measured values
Inject a current, which is less than the relay pickupcur-
rent set values, in phase 1 (terminals B3-B4), and
check the measured current on the display by pressing
the push button <SELECT>. For a relay with rated cur-
rent In = 5A, for example, a secondary current injec-
tion of 1A should be indicated on the display with
about 0.2 (0.2 x In). The current can be also injected
into the other current input circuits (Phase 2: terminals
B5-B6, Phase 3: terminals B7-B8. Compare the dis-
played current value with the reading of the ammeter.
The deviation must not exceed 3% or 1 % In. By using
an RMS-metering instrument, a greater deviation may
be observed if the test current contains harmonics. Be-
cause the MRI1 relay measures only the fundamental
component of the input signals, the harmonics will be
rejected by the internal DFFT-digital filter. Whereas the
RMS-metering instrument measures the RMS-value of
the input signals.
6.4.4 Checking the operating and
resetting values of the relay
Inject a current which is less than the relay set values in
phase 1 of the relay and gradually increase the cur-
rent until the relay starts, i.e. at the moment when the
LED I> and L1 light up or the alarm output relay I> is
activated. Read the operating current indicated by the
ammeter. The deviation must not exceed 3 % of the set
operating value or 1 % In.
Furthermore, gradually decrease the current until the re-
lay resets, i.e. the alarm output relay I> is disengaged.
Check that the resetting current is smaller than 0.97
times the operating current.
Repeat the test on phase 2, phase 3 and earth current
input circuits in the same manner.(Accuracy of earth
current measuring ±3% of measuring value or
0.1% of In for E-type; 0.01% of In for X-type).