TD_MRI1_06.05_GB 39
Setting list MRI1
Note !
All settings must be checked at site and should the occasion arise, adjusted to the object / item to be protected.
Project:
SEG job.-no.:
Function group: =
Location: + Relay code: -
Relay functions:
Password:
Date:
Relay type MRI1- I IE
IX
IRE
IRX
IR IER
IXR
IRER
IRXR
ER
XR
E
X
ISR IRSR SR Default
settings
Actual
settings
I> X X X X X X X X 0.2 x I
N
CHAR I> X X X X X X X X DEFT
t
I>V
/t
I>R
X X X X X X X X 0.03 s
0s /60 s (phase) X X X X X X X X 0 s
I>> X X X X X X X X 1.0 x I
N
t
I>>V
/t
I>>R
X X X X X X X X 0.03 s
RCA X X X X 49 °
3pha/e-n/1:1 X X X 3 pha
U
E
X X X 1V/2V/5V
I
E>
X X X X X X X X X
0.01 x I
N
(E)
0.1% I
N
(X)
WARN/TRIP X X X X X X TRIP
CHAR I
E
X X X X X X DEFT
t
IE>V
/t
IE>R
X X X X X X X X X
0.05 s
(ER/XR)
0.04 s (others)
0s / 60 s (earth) X X X X X X 0 s
I
E>>
X X X X X X X X X
0.01 x I
N
(E)
0.1% I
N
(X)
t
IE>>V
/t
IE>>R
X X X X X X X X X
0.05 s
(ER/XR)
0.04 s (others)
SIN/COS X X X SIN
SOLI/RESI X X X SOLI
t
CBFP
X X X X X X X X X X X 0,1 s
50/60 Hz X X X X X X X X X X X 50 Hz
Indication activation X X X X X X X X X X X FLSH
RS 485 / Slave-
address
X X X X X X X X X X X 1
Baud-Rate* X X X X X X X X X X X 9600
Parity-Check* X X X X X X X X X X X even
Blocking function X X X X X X X X X X X
Assignment of the
output relays
X X X X X X X X X X X
Failure memory X X X X X X X X
* only Modbus Protocol
All settings must be checked at site and should the occarision arise, adjusted to the object/item to be protected.