4 TD_MRI1_06.05_GB
1 Introduction and application
The MRl1 digital multifunctional relay is a universal
time overcurrent and earth fault protection device in-
tended for use in medium-voltage systems, either with
an isolated/compensated neutral point or for networks
with a solidly earthed/resistance-earthed neutral point.
The protective functions of MRI1 which are imple-
mented in only one device are summarized as fol-
lows:
Independent (Definite) time overcurrent relay.
Inverse time overcurrent relay with selectable charac-
teristics.
Integrated determination of fault direction for appli-
cation to doubly infeeded lines or meshed systems.
Two-element (low and high set) earth fault protection
with definite or inverse time characteristics.
Integrated determination of earth fault direction for
application to power system networks with isolated
or arc suppressing coil (Peterson coil) neutral
earthing. (ER/XR-relay type).
Integrated determination of earth short-circuit fault di-
rection in systems with solidly-earthed neutral point or
in resistance-earthed systems (SR-relay type).
Furthermore, the relay MRI1 can be employed as a
back-up protection for distance and differential protec-
tive relays.
A similar, but simplified version of overcurrent relay
IRI1 with limited functions without display and serial in-
terface is also available.
Important:
For additional common data of all MR-relays please
refer to manual "MR - Digital Multifunctional relays".
On page 41 of this manual you can find the valid soft-
ware versions.
2 Features and characteristics
Digital filtering of the measured values by using dis-
crete Fourier analysis to suppress the high frequence
harmonics and DC components induced by faults or
system operations
Selectable protective functions between:
definite time overcurrent relay and
inverse time overcurrent relay
Selectable inverse time characteristics according to
BS 142 and IEC 255-4:
Normal Inverse
Very Inverse
Extremely Inverse
Reset setting for inverse time characteristics select-
able
High set overcurrent unit with instantaneous or de-
finite time function.
Two-element (low and high set) overcurrent relay
both for phase and earth faults.
Directional feature for application to the doubly in-
feeded lines or meshed systems.
Earth fault directional feature selectable for either iso-
lated or compensated networks.
sensitive earth fault current measuring with or without
directional feature (X and XR-relay type
Determination of earth short-circuit fault direction for
systems with solidly-earthed or resistance-earthed
neutral point.
Numerical display of setting values, actual mea-
sured values and their active, reactive components,
memorized fault data, etc.
Withdrawable modules with automatic short circuit
of C.T. inputs when modules are withdrawn.
Blocking e.g. of high set element (e.g. for selective
fault detection through minor overcurrent protection
units after unsuccessful AR).
Relay characteristic angle for phase current direc-
tional feature selectable
Dwell time selectable
Switch failure protection
Storage of tripping values and shut-down times
(not ER/XR versions) (t
CBFP
) of eight failure events
Free assignment of output relays
Serial data exchange via RS485 interface possible;
alternatively with SEG RS485 Pro-Open Data Proto-
col or Modbus Protocol
Suppression of indication after an activation
(LED flash)