Doc name : OP INST PIC152N OP168 V04 (Page 2 of 4)
FUNCTIONS MENU
ALARM MODULE ( ALARM 1)
( to scroll through functions / )
ALARM MODULE ( ALARM 2)
( to scroll through functions / )
Manual
Lower limit
Upper limit
Analog
output %
*ANALOG O/P MODULE
(To change function / )
Appearance of all shaded menus dependent on selection of other parameters.
Refer programming for further details.
*-Applicable only for analog output models.
Alarm mode
Latch
Hold
Alarm status
Alarm
annunciator
Alarm
annunciator
Alarm
hysteresis
Alarm
hysteresis
Alarm high
limit
Alarm
low limit
Alarm mode
Latch
Hold
Alarm status
Alarm
high limit
Alarm
low limit
Input type
Temp. Unit
Resolution
Filter time
constant
INPUT PARAMETERS
( to scroll through functions press / )
Sensor error
level
Display scaling
(low)
Input scaling
(low)
Display scaling
high)(
Input scaling
high)(
Reverse scaling
S.P. High limit
S.P. Low limit
Reset
Lock code
PV Bias
TO CHANGE LEVELS PRESS OR
+
+
KEY PRESS DISPLAY
DESCRIPTION
KEY PRESS DISPLAY
DESCRIPTION
KEY PRESS DISPLAY
DESCRIPTION
NOTE : This parameter is not prompted if analog input is selected.
Default setting : C
O
Press key to select Temperature unit
Value displayed in
O
C
Value displayed in F
O
Display
Display
Display
Display
for 1 sec.
for 1 sec.
for 1 sec.
for 1 sec.
Temperature Unit
Press +
Press +
Press key to select Resolution
Default value : 1
NOTE : This parameter is not prompted if input is R, S type thermocouple.
Range : 1 / 0.1 for TC / RTD
1 / 0.1 / 0.01 / 0.001 for AIN
Resolution
Range : OFF, 1 to 99 sec.
Filter time constant *
For AIN display as per decimal point selected.
PV bias *
Default value : 0.0
Press key to select PV bias
Range : -200 to 200
(fixed 0.1 C for TC/RTD)
o
Default value : 1sec.
Press key to select Filter time constant
to change value
Press + /
Press +
/
to change value
Press key to select Display value scaling point1
Default value : 0
Display value scaling
point low (DSCL) *
Display
Display
for 1sec
for 1sec.
Range : -1999 to DSCH
ForAINdisplayasper
decimal point selected.
NOTE : This parameter is not prompted if TC/RTD input types
are selected
Press + /
Press +
/
Press +
/
to change value
Input value scaling
point low (ISCL) *
NOTE : This parameter is not prompted if TC/RTD input types
are selected
Default value : 0.00
Range : 0.0mA / -5mV /
0.0 V to ISCH
(default value changes as per
analog input selected)
Press key to select input value scaling point 1
Display
for 1sec.
NOTE : This parameter is not prompted if TC/RTD input types
are selected
Press key to select Display value scaling point 2
Range : DSCL to 9999
For AIN display as per decimal
point selected.
Default value : 9999
Display value
scaling point high
(DSCH) *
to change value
to change value
* mark explained in the user guide
AIN - Analog Input
Note : .
KEY PRESS DISPLAY
DESCRIPTION
Input value scaling
point high (ISCH) *
Range : ISCL to 20.00mA
/ 56mV / 10.00V
(default value changes as per
analog input selected)
Press key to select Input value scaling point 2
Default value : 20.0mA
NOTE : This parameter is not prompted if TC/RTD input types
are selected
Press + /
Press +
/
Press +
Press +
Display
Display
to change value
for 1 sec.
for 1 sec.
Reverse scaling*
The display scaling point
settings can be reversed
by selecting Reverse
scaling as
Press key to select Reverse scaling
Default setting :
NOTE : This parameter is not prompted if TC/RTD input types
are selected
Press key to select Set point high limit
Default value : 750 C
o
Display
Display
Display
Display
for 1sec
for 1sec
for 1sec
for 1sec
Set point high
limit (SPHL)
Range : SPLL to max.
range of sensor
SPLL to DPSH
(for TC/RTD)
(for AIN) for AIN display as per
decimal point selected.
Set point low
limit
(SPLL)
Range : min. range of
sensor to SPHL
DSCL to SPHL
(for TC/RTD)
(for AIN) for AIN display as
per decimal point selected.
Lock code
Range : 0 to 9999
Press key to select Set point low limit
Default value : -200 C
o
to change value
Press + /
to change value
Press + /
to change value
Press key to select Lock code
Default setting : 0
Press + /
to change value
Press key to select Reset
Reset
All parameters set to
factory setting
Default setting :
Press + till Level 1 is displayed
NOTE : Programming steps for
Level2 ( ) is same
Level1 (
) &
Alarm1
module Alarm2 module .
Programming of level1 is shown.
PROGRAMMING OF LEVEL 1
NOTE : After altering the value of the input parameters
press or for change to actually take effect.
Range : LA to SPHL
SPLL to SPHL
(BAND mode)
(HA mode)
for AIN display as per decimal
point selected.
NOTE : This parameter is not prompted if alarm mode is
/ / /
Default value : 750 C
o
Press key to select Alarm high limit
Alarm high limit
Parameters in this level
can be set.
Display
Display
for 1sec
for 1sec
Range : SPHL to HA
(BAND mode)
SPLL to SPHL
(LA mode)
for AIN display as per
decimal point selected.
Default value : -200 C
o
Alarm low limit
Press key to select Alarm low limit
Press key to select Alarm hysteresis.
Range: 0.1 to 99.9 C
1 to 999
o
(for TC/RTD)
(for analog input)
for AIN display as per decimal
point selected.
Default value: 1.0
Alarm hysteresis
Press + /
to change value
Press + /
to change value
NOTE : This parameter is not prompted if alarm mode is
/ / /
NOTE : This parameter is not prompted if alarm mode is
/ /
Display